case studies

Ammonia Condenser

Before

Before

Before

Before Sustainachem Started Treating the System:

  • Calcium cycles were 1.65 with conductivity cycles at 2.6 (Scale Forming)
  • Iron levels were 1.31 ppm (Under Deposit Corrosion)
  • Zinc levels 1.4 ppm (White Rust)
  • Ammonia leak in the system (High Acid Feed and Blowdown Masking)
  • Feeding sulfuric acid (Overfeeding due to leak)
  • Sulfate reducing bacteria and legionella present
  • Spending $115,000 on water treatment chemicals
  • Fans running hard due to poor heat transfer


After

Before

Before

After Sustainachem Took Over (10 Months)

  • Calcium cycles 4.1 and conductivity cycles 3.8 (Removing Scale)
  • Iron levels - 0 ppm
  • Zinc levels - 0 ppm
  • Changed acid feed 
  • Added proper biocides and cleaned up system
  • No legionella present
  • Spending less than 1/2 of previous spend
  • Water savings of 3 MGal/yr by cycling and fixing leaks
  • Energy savings of $62,800 from clean coil

HVAC LOOP

Extremely High Iron

Extremely High Iron

Extremely High Iron

Before Sustainachem Took Over the Site:

  • Filters were being changed out every two weeks as seen above
  • Iron levels were 311 ppm total with 171 ppm FE2+ (Corrosion)
  • Plugged strainers and coils restricting flow
  • Overworking compressors and leading to failure of 3-4/yr
  • Spending $45k/yr on replacement heat pumps


Quick Turn Around

Extremely High Iron

Extremely High Iron

After Sustainachem Took Over:

  • Picture above is after 24 hours of treatment
  • Iron was down from 311 ppm to 17 ppm
  • After 4 days iron was down to 0 ppm soluble
  • Filters no longer being replaced as they are clean
  • No plugged strainers
  • No more replacement compressors